中文  |   EN
+86-0531-61360166
中文 |  EN
Product Categories

Current Location:Home > Product > Sensing terminals > Gas Detection

Hydrogen sulfide detector

TEL:+86-0531-61360166 +86-0531-61360266

Hydrogen sulfide detector
资料更新中...
Order Hotline:+86-0531-61360166 +86-0531-61360266
Product Description

Hydrogen sulfide concentration detector is an explosion-proof hydrogen sulfide gas detector developed and produced by our company according to industrial grade design standards, which can be directly installed in hazardous areas of Zone 1 and Zone 2; aluminum alloy explosion-proof casing, durable; support 24-hour continuous online monitoring; 12-30V wide voltage DC power supply; RS485 signal output, supporting long-distance data telemetry; built-in imported brand hydrogen sulfide gas sensor probe, high precision, strong stability, low error rate; full range of temperature compensation, to ensure long-term stability and reliability of the measurement value; comes with automatic correction function of zero point in the air, to ensure that the product does not appear false alarm phenomenon in the process of use.
This Hydrogen sulfide concentration detector has excellent performance, With high stability and easy installation and maintenance, it greatly meets the requirements of industrial site safety monitoring for high reliability of equipment, and is widely used in various places such as indoor chemical product workshops (chemical plants, pharmaceutical plants), chemical product and pharmaceutical warehouses, cable and cosmetic plants, food plants, wineries, laboratories, coal mines, substations, etc.

Operating Voltage

24 VDC

Measurement Range

0-500, 1000, 2000, and 5000 ppm possible choice

OVF

1ppm

line spacing

≤±2%

Gas extraction method

Natural diffusion type

Design life

2 to 5 years

Transmission method

RS485, Modbus RTU

Operating temperature

0℃~+50℃

Working humidity

10~95%RH

Work stress

86~106Kpa

Design Standards

GB 50493-2009 "Design Specification for Detection and Alarm of Combustible and Toxic Gases in Petrochemical Enterprises
GB 12358-2006 General Technical Requirements for Environmental Gas Detection and Alarm Instruments in Workplaces

Implementation Standards

GB3836.1-2010《Electrical Equipment for Explosive Gas Environments Part I: General Requirements》
GB3836.2-2010《Electrical equipment for explosive atmospheres Part II: Explosion-proof type "d" 》

GB12358-2006 《General Technical Requirements for Environmental Gas Detection and Alarm Devices in Workplaces》
GBZ 2.1-2007 《Occupational exposure limits for harmful factors in the workplace》
GB 4208-2008 《Enclosure Protection Rating (IP Code)》

GB 12476.1-2013 Electrical equipment for combustible dust environment Part 1: General requirements

GB 12476.1-2013 Electrical equipment for combustible dust environments Part 5: Enclosure protection type "tD"

Explosion-proof grade

Exd IICT6 Gb/Ex tD A21 IP66 T80℃

Protection level

IP66